Fire Pump Rooms that pass first time — design once, test cleanly 🎯 Purpose Provide code‑reliable water flow and pressure to sprinklers and standpipes during fire. Operate under loss of power and single faults, without operator intervention. (NFPA 20, NFPA 13, NFPA 14) 🧩 Anatomy / Components • Fire pump (diesel or electric) with listed controller. • Suction from tank with anti‑vortex plate and air‑release at high point. (NFPA 22) • Eccentric reducer flat‑on‑top and long, straight approach to the eye. • Discharge check + OS&Y gate, relief to safe drain/test header. • Jockey pump + pressure switch to maintain setpoint. • Test header/flowmeter line, gauges on suction/discharge, trench to drain. • Signals to FACP: pump run, controller trouble, phase loss, low fuel. 📐 Setpoints & Specs • Suction velocity ≤ 1.8 m/s; straight length ≥ 5–10 × suction Ø. • Anti‑vortex plate diameter ≈ 2 × outlet; elevation ≥ 0.5 × outlet above floor. • Normal pressure band: jockey ± ...